datasheetbank_Logo
전자부품 반도체 검색엔진( 무료 PDF 다운로드 ) - 데이터시트뱅크

K8AB-PA 데이터 시트보기 (PDF) - OMRON Corporation

부품명
상세내역
일치하는 목록
K8AB-PA Datasheet PDF : 11 Pages
1 2 3 4 5 6 7 8 9 10
K8AB-PA
Setting Method
1. Asymmetry
Asymmetry is set using the asymmetry operation knob (ASY.)
The setting can be between 2% and 22% of the rated input.
Turn the knob while there is an input to the input terminals until the alarm indicator flashes (when the set value and the input have reached the
same level.)
Use this as a guide to set the asymmetry.
The rated input depends on the model and DIP switch setting.
Example: K8AB-PA1 with Pin 2 Turned OFF (Three-phase, Three-wire Mode) and Pins 3 and 4 Turned OFF (Rated Voltage of 200 V)
The rated input voltage is 200 VAC and the setting range is 4 to 44 V.
If the setting (ASY. knob) is at 10%, the asymmetry operation voltage is 20 V and an alarm will be output if the difference between
the minimum and maximum phases for two of the three phases exceeds 20 V.
2. Operating Time
The operating time is set using the operating time knob (T).
The operating time can be set to between 0.1 and 30 s.
Turn the knob while there is an input to the input terminals until the alarm indicator flashes (when the set value and the input have reached the
same level.)
Use this as a guide to set the operating time.
If the input exceeds the asymmetry set value, the alarm indicator will start flashing for the set period and then stay lit.
Dimensions
Three-phase Asymmetry and Phase-sequence Phase-loss Relay
K8AB-PA1
K8AB-PA2
22.5
100
(Unit: mm)
5
90
72
5
8

Share Link: 

datasheetbank.com [ Privacy Policy ] [ Request Datasheet ] [ Contact Us ]