Nomenclature
Front
Terminal block
(See notes 1 and 2.)
Power indicator
Relay status indicator
Alarm indicator
Asymmetry rate knob
(ASY.)
Operating time knob (T)
Terminal block
(See notes 1 and 2.)
K8AB-PA
Indicators
Item
Meaning
Power indicator
(PWR: Green)
Lit when power is being supplied (see note).
Relay status indicator Lit when relay is operating (normally lit).
(RY: Yellow)
Alarm indicator
(ALM: Red)
Asymmetry voltage error indicator
The indicator flashes to indicate the error status after
the input has exceeded the threshold value while the
operating time is being clocked.
Note: The input across L1 and L2 is used for the internal power
supply. Therefore, the power indicator will not be lit if there is no
input across L1 and L2.
Setting Knobs
Item
Asymmetry rate knob
(ASY.)
Operating time knob (T)
Usage
Used to set the asymmetry rate to 2% to 22%.
Used to set the operating time to 0.1 to 30 s.
Note: 1. Use either a solid wire of 2.5 mm2 maximum or a ferrule with
insulating sleeve for the terminal connection.
The length of the exposed current-carrying part inserted
into the terminal must be 8 mm or less to maintain dielectric
strength after connection.
For 2.5 mm2 or
smaller solid wires
For ferrules with
insulating sleeves
8 mm max.
Recommended ferrules
Phoenix Contact
Al 1,5-8BK (for AWG16)
Al 1-8RD (for AWG18)
Al 0,75-8GY (for AWG18)
2. Tightening torque
Recommended: 0.49 N·m
Maximum: 0.54 N·m
8 mm max.
6