Connections
K8AB-PA
Wiring Diagram
Voltage Asymmetry and Phase Sequence/Phase Loss Operation Diagram
L1
Input L2
L3
Asymmetry operation voltage (set value)
Alarm indicator
Flashing
Lit
Relay
L1
Input L2
L3
Alarm indicator
T T: Operating time (0.1 to 30 s)
T1: Power ON lock (1 s or 5 s)
T1
Phase loss operation
Phase sequence operation
L1 L3 L1
L3 L2 L2
L2 L1 L3
Flashing Flashing
Relay
Note: 1. K8AB-PA output relay is normally operative.
2. The power ON lock prevents unnecessary alarms from being generated during
the instable period when the power is first turned on. There is no relay output
during timer operation.
3. Phase loss is detected by L1, L2, and L3 voltage drops.
A phase loss will exist if any of the phases drops below 60% of the rated input.
4. L1 and L2 function both as the power supply terminals and as input terminals.
If the voltage drops dramatically, then the Relay will not operate due to an
undervoltage.
5. Motor load phase loss cannot be detected during operation.
6. Phase loss is detected based on voltage, so phase loss cannot be detected on
the load side.
Calculating the Asymmetry Operating Voltage
Asymmetry operation condition = (Highest voltage Lowest voltage) > Asymmetry operating voltage
Asymmetry operating voltage = Rated input voltage (V) × Asymmetry set value (%)
Note: The rated input voltage is selected and set with the DIP switch.
N L1 L2 L3
Voltage input
L1
L2
N
L3
14
Signal output
11
12 Relay signal
output
Load
Operation Indicators
Item
Display
Contact
operation
Ry_LED Alarm_LED Alarm_LED
Asymmetry OFF
ON
OFF
Phase loss OFF
ON
OFF
Reversed OFF
phase
Flashing OFF
(See note.)
Correct
ON
phase
OFF
ON
Note: The indicator will flash once per second after a phase loss is
detected and once per 0.5 second during the detection time.
5