NC1V Circuit Protectors
IDEC’s original spring-up, fingersafe terminals enhance reliability and safety.
Integrated electric shock protection structure (IP20).
Auxiliary/alarm contact terminals and voltage coil terminals on
the relay trip types are equipped with terminal covers.
Spring-up, fingersafe terminals reduce wiring time.
Ring terminals can be installed. Captive terminal screws.
Available with inertia delay
Available with auxiliary or alarm contacts
Rated short-circuit capacity: 2500A
Slim, space-saving housing
1-pole: 17.5mm wide
2-pole: 35.0mm wide
3-pole: 52.5mm wide
Retractable actuator
The trip-free mechanism maintains the circuit open even
when the operator is turned on after tripping.
Applicable Standards
Certification Mark
Certification Organization
(File No.)
UL1077
E68029
CSA C22.2 No. 235
LR83454
EN60934
GB17701-1999
B07 09 13332 063
European Commission's
Low Voltage Directive
No. 2008010307265840
Electrical Applicance and Series Trip
Material Safety Law
JET
Technical Standard
Relay Trip
Note: TÜV, CE, and CCC marks are applicable for series trip type only.
Specifications
Operator Style
Retractable actuator
Internal Circuit
Series trip (current trip), Relay trip (voltage trip)
Protection Method
Hydraulic magnetic tripping system, Magnetic tripping system (voltage trip)
No. of Poles
1-pole
2-pole
3-pole
Rated Voltage (AC/DC)
(Note 1)
Series Trip
(Current Trip)
Rated Short-circuit
Capacity
Rated Current
Operation Characteristics
(Note 2)
Relay Trip
Rated Current
(Voltage Trip)
(Note 3) Trip Voltage
Auxiliary Contact/
Alarm Contact
Contact Rating
Minimum Applicable Load
250V AC 50/60Hz, 65V DC
250V AC 50/60Hz, 125V DC
250V AC, 50/60Hz
250V AC, 2500A
65V DC, 2500A
250V AC, 2500A
125V DC, 2500A
250V AC, 2500A
0.1A, 0.3A, 0.5A, 1A, 2A, 3A, 5A, 7A, 10A, 15A, 20A, 25A, 30A
Time delay curve curve M (slow), curve A (medium), S (instantaneous)
Curves M and A are avilable with inertia delay.
30A
24 to 48V DC (at 25°C)
Voltage application duration 10 sec maximum, tripping time 0.1 sec maximum (at rated voltage)
125V AC 3A (resistive load), 30V DC 2A (resistive load)
24V DC 1mA (resistive load, reference value)
Insulation Resistance
Dielectric Strength
Vibration Resistance
(with rated current applied)
100 MΩ minimum (500V DC megger)
2000V AC, 1 minute (between terminals when main contacts are open, between live parts of different
poles, between live and dead parts)
600V AC (between terminals when auxiliary circuits are open)
Damage limits:
147 m/s2 (10 to 55 Hz) (1-pole, 2-pole), 78 m/s2 (3-pole)
Operating extremes: 98 m/s2 (1-pole, 2-pole), 78 m/s2 (3-pole)
Shock Resistance
(S time delay curve: 80% rated current,
A, M time delay curve: 100% rated current)
Damage limits:
490 m/s2 (1-pole, 2-pole), 297 m/s2 (3-pole)
Operating extremes: 196 m/s2 (S, A, M types)
Electrical Life
10,000 cyles minimum (at rated curent), 10 operations per minute
Reference Temperature
40°C
Operating Tempperature
10 to +60°C (no freezing)
Rated current is based on an ambient temperature of 40°C. When the operating temperature exceeds
40°C, derate the rated current by using the factors shown below.
Operating Humidity
45 to 85% RH (no condensation)
Main Circuit Terminal
Terminal Style Auxiliary/Alarm Contacts,
Voltage Coil Terminal
Weight (approx.)
Spring-up, fingersafe terminal: M4 screw (up to 20A), M5 screw (25A and 30A)
M3.5 screw
1-pole: 90g, 2-pole: 170g, 3-pole: 260g
Note 1: 3-pole type is for AC voltage only.
Note 2: For S (instantaneous) tripping curve, humming sound may be caused when used in an AC sinusoidal-wave current circuit around 80% of
the rated current, however, the performance of the circuit protector will not be affected.
To avoid unnecessary tripping, do not use in circuits where inrush currents may be present.
Note 3: Relay trip (voltage trip) type is not equipped with an overcurrent trip function.
Do not use the NC1V circuit protectors in environments where they are exposed to extreme temperature, humidity, dust, corrosive gases,
vibration, shock, or in a circuit where inrush current may be present, otherwise unnecessary operations and damage may occur.
Operating Temp. Derating Factor
50°C
0.9
55°C
0.8
60°C
0.7
4