datasheetbank_Logo
전자부품 반도체 검색엔진( 무료 PDF 다운로드 ) - 데이터시트뱅크

NC1V-3513-7AS 데이터 시트보기 (PDF) - Unspecified

부품명
상세내역
일치하는 목록
NC1V-3513-7AS
ETC
Unspecified ETC
NC1V-3513-7AS Datasheet PDF : 12 Pages
First Prev 11 12
NC1V Circuit Protectors
3-pole
47.0
6.6
M5 Terminal Screw (30A)
66.0
48.3
DIN Rail (BNDN1000)
All dimensions in mm.
Mounting Hole Layout
(M4 Mounting Screws)
47.0
NC1V-3500
(Relay Trip)
ON
M3.5 Terminal Screw
2-ø4.5 Holes
(for screw mounting)
52.5
Terminal Cover
5.0
33.0
2-M4
Instructions
Installation Angle
Tripping method is hydraulic magnetic. Minimum operating
current varies with installation angle. Operating currents
are influenced by the weight of movable iron core. With
reference to the following figures, correct the rated current.
100%
120%
90%
100%
Minimum operating current is calculated from the following
formula:
(Minimum operating current) = (Rated current) ×
(Correction factor by installation angle) × (Reference
minimum tripping current rate)
DIN Rails
[Installation on DIN Rail]
1. Fasten the DIN rail securely.
2. With the latch facing downward, install the NC1V circuit
protector on the DIN rail as shown below.
[Removal from DIN Rail]
Using a flat screwdriver, pull the latch on the circuit
protector to remove from the DIN rail.
Installing
35mm-wide
DIN Rail
Removing
35mm-wide
DIN Rail
Push
Flat
Srcrewdriver
Latch
Applicable Wire and Crimp Terminal
Terminal
Terminal Screw
Connectable Applicable
Wire Size Crimping
(mm2)
Terminal
Spring-up, fingersafe,
slotted Phillips screw
with square washer
(up to 20A)
0.25 to 1.65
1.04 to 2.63
2.63 to 6.64
R1.25-4
R2-4
R5.5-4
Spring-up fingersafe
terminal
(25A and 30A)
0.25 to 1.65
1.04 to 2.63
2.63 to 6.64
R1.25-5
R2-5
R5.5-5
Tightening
Torque
(N·m)
1 to 1.4
1.8 to 2.2
Slotted Phillips screw
with square washer
0.25 to 1.65
1.04 to 2.63
R1.25-3.5
R2-3.5
0.7 to 0.9
For wiring the main circuit terminal, use the applicable crimp terminals and
tighten to the recommended torque.
When using the NC1V circuit protector as CSA-certified product, use with CSA-
certified crimp terminal.
When using the NC1V circuit protector as UL-listed product, use with UL-listed
crimp terminal.
Panel Mounting Screw (not supplied)
Srew Type
Tightening Torque
Shape
Spring Washer
M4
0.8 to 1.0 N·m
Plain Washer
Product Markings (Example: NC1V-1111-30AA)
Type No.
Rated Voltage
Rated Current
PSE Certification
PS
E
JET
220VAC 30A I.C.2500A
CIRCUIT PROTECTOR
NC1V-1111
POLE 1
Ue 250VAC 50/60Hz · 65VDC
In 30A
CURVE A
Suppl. Prot.
AUX. SW
125VAC 3A
30 VDC 2A
A.T. 40°C
JAPAN
No. of Poles
Time Delay Curve
Auxiliary/Alarm Contact Rating
Reference Operating
Temperature
Certification Marks
Installation of Auxiliary/Alarm Terminal Cover
After wiring the terminals, install the terminal cover by
aligning with the circuit protector as shown below.
Terminal cover installed
11

Share Link: 