Controlled Ventilation
Ventilation is an important part of maintaining a comfortable,
healthy, productive environment for people. Improper
ventilation can have a negative impact on occupant health
and performance, increase the risk from litigation, and/
or waste energy. Demand-controlled ventilation using CO2
sensors prevents energy losses from over-ventilation while
maintaining indoor air quality. The most energy savings
potential is in buildings where occupancy fluctuates during
a 24-hour period. Numerous organizations now require and/
or recommend CO2-based ventilation control in different
commercial HVAC applications. Some utility companies also
offer rebates to building owners for installing CO2 sensors.
Wall mount sensors are used to control a specific area such
as a conference room, classroom, meeting hall, etc. The
Telaire 8000-R Ventostat series are easy to install and have a
clean, modern look that suits most indoor environments.
Wall Mount Specifications
Sensing Method
• Non-dispersive infrared (NDIR) absorption
• Gold-plated optics
• Patented ABC Logic self calibration algorithm
CO2 Measurement Range
8100-R 0 to 2000 ppm
8200-R 0 to 5000 ppm
(0 ppm = 0 V, 4 mA)
CO2 Accuracy
±30 ppm or 3% of the reading shown, whichever is higher *
Active Temperature Accuracy /Range
0-50°C (32-122°F)
±1°C from 15-30°C (±1.8°F from 59 to 86°F)
Power Supply Requirements
18-30 VAC RMS, 50/60 Hz, or 18 to 42 VDC,
polarity protected
Warranty
24 months on mechanical defects
Calibration - lifetime warranty (ABC Logic on.)
Certifications
CE EMC, RoHS, REACH and WEEE compliant
Signal Update
Every 5 seconds
CO2 Warm-up Time
• < 2 minutes (operational)
• 10 minutes (maximum accuracy)
Operating Conditions
• 32°F to 122°F (0°C to 50°C)
• 0 to 95% RH, non-condensing
Storage Conditions
-40°F to 158°F (-40°C to 70°C)
Flammability Classification
UL94 5VA
Relay
Normally open and normally close contacts
Rated Load
0.50 A at 125 VAC, 1A 24 VDC
Contact Material
Ag + Au-Alloy
Carry current 2 A
Max. Operating Voltage
125 VAC, 60 VDC
Max. Operating Current
1A
Max. Switching Capacity
62.50 VA
*AHRAE — regulation 62 states maximum indoor CO2
level of 1000 ppm
Power Consumption
Typical 0.7 W at nominal voltage of 24V AC RMS
Temperature Dependence
0.2% FS per °C (±0.11% per °F)
Stability
<2% of FS over life of sensor (15 years)
Pressure Dependence
0.135% of reading per mm Hg
Output
Analog (Temperature and CO2)
• 0 to 5 V, or 0 to 10 V switch selectable (100 Ω output
impedance)
• Or 4 to 20 mA (RL maximum 500 Ω)
• Voltage and current outputs are not available
simultaneously
• Digital to analog error ±2%
*C02 accuracy statement excludes standard gas used for
calibration that has an accuracy of 2%. In addition, there is a
potential digital to analog error of up to 2%.