120W Single Output Industrial DIN RAIL
EDR-120 series
SPECIFICATION
MODEL
EDR-120-12
EDR-120-24
EDR-120-48
DC VOLTAGE
12V
24V
48V
RATED CURRENT
10A
5A
2.5A
CURRENT RANGE
0 ~ 10A
0 ~ 5A
0 ~ 2.5A
RATED POWER
120W
120W
120W
RIPPLE & NOISE (max.) Note.2 100mVp-p
120mVp-p
150mVp-p
OUTPUT VOLTAGE ADJ. RANGE
12 ~ 14V
VOLTAGE TOLERANCE Note.3 ±2.0%
24 ~ 28V
±1.0%
48 ~ 55V
±1.0%
LINE REGULATION
±0.5%
±0.5%
±0.5%
LOAD REGULATION
±1.0%
±1.0%
±1.0%
SETUP, RISE TIME
1200ms, 60ms/230VAC 2500ms, 60ms/115VAC at full load
HOLD UP TIME (Typ.)
16ms/230VAC 10ms/115VAC at full load
VOLTAGE RANGE Note.6 90 ~ 264VAC 127 ~ 370VDC
[DC input operation possible by connecting AC/L(+), AC/N(-)]
FREQUENCY RANGE
47 ~ 63Hz
INPUT
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
85%
2.25A/115VAC
20A/115VAC
1.3A/230VAC
35A/230VAC
87.5%
88.5%
LEAKAGE CURRENT
<1mA / 240VAC
OVERLOAD
105 ~ 130% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
PROTECTION
OVER VOLTAGE
14 ~ 17V
29 ~ 33V
Protection type : Shut down o/p voltage, re-power on to recover
56 ~ 65V
OVER TEMPERATURE
Shut down o/p voltage, re-power on to recover
WORKING TEMP.
-20 ~ +60(Refer to "Derating Curve")
WORKING HUMIDITY
20 ~ 95% RH non-condensing
ENVIRONMENT STORAGE TEMP., HUMIDITY -40 ~ +85, 10 ~ 95% RH
TEMP. COEFFICIENT
VIBRATION
±0.03%/(0 ~ 50)
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
SAFETY STANDARDS
SAFETY & WITHSTAND VOLTAGE
EMC
(Note 4)
ISOLATION RESISTANCE
EMC EMISSION
Ul508, TUV EN60950-1 approved;(meet EN60204-1)
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25/ 70% RH
Compliance to EN55022 (CISPR22) Class A, EN61000-3-2,-3
EMC IMMUNITY
MTBF
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
474.6K hrs min. MIL-HDBK-217F (25)
OTHERS
NOTE
DIMENSION
40*125.2*113.5mm (W*H*D)
PACKING
0.6Kg; 20pcs/13Kg/1.16CUFT








File Name:EDR-120-SPEC 2015-10-29