Industrial Power Supplies
TIS Series
50–600 Watt
Power Supplies with Powerfail Functions
These models provide 3 functions required in many process control system applications:
AC-Powerfail signal (relay contact)
Power Good signal (relay contact)
Remote On/Off
Models
Order Code
(includes terminal plugs)
TIS 150-124 SIG
TIS 150-148 SIG
TIS 300-124 SIG
TIS 300-148 SIG
TIS 600-124 SIG
TIS 600-148 SIG
Input Voltage
115/230 VAC
selectable
115/230 VAC
selectable
115/230 VAC
selectable
Output Power
max.
150 W
300 W
600 W
Output Voltage
nom.
24 VDC
48 VDC
24 VDC
48 VDC
24 VDC
48 VDC
Output Current
max.
6.0 A
3.0 A
12 A
6.0 A
24 A
12 A
Con1
L Pin3
Con1
N Pin2
AC
DC
Con1
Pin1
Remote
ON/OFF
Con2 - Pin3/4 +Vout
Output
OK
Con2 - Pin1/2 -Vout
Con3 - Pin2 +
Con3 - Pin1
-
Mains
Fail
Detection
(Relay A)
Power Good
Detection
(Relay B)
Con3 - Pin7
Con3 - Pin6
Common
AC-Powerfail
Mains OK
Con3 - Pin5
Con3 - Pin4
Con3 - Pin3
Power Good
Common
Power Good
Power Good
Specifications
Power Good signal trigger point
models with 24 Vout: >22.8 VDC ±0.5 V relay B closed (pin 4 – pin 3)
models with 48 Vout: >45.6 VDC ±1.0 V relay B closed (pin 4 – pin 3)
AC-Powerfail signal Vin <93 resp. <187 VAC relay A closed
(pin 7 – pin 6)
Raiting per relay contact 60 VDC /0.36 A max.
Remote On/Off
– On
short circuit con 3 pin 1 and pin 2
– Off open circuit con 3 pin 1 and pin 2
Instruction manual for SIG option can be downloaded under:
http://www.tracopower.com/products/tis-sig_manual.pdf
http://www.tracopower.com
Page 5 of 12