datasheetbank_Logo
전자부품 반도체 검색엔진( 무료 PDF 다운로드 ) - 데이터시트뱅크

LF505-S 데이터 시트보기 (PDF) - LEM Industrial

부품명
상세내역
일치하는 목록
LF505-S
LEM
LEM Industrial LEM
LF505-S Datasheet PDF : 3 Pages
1 2 3
Current Transducer LF 505-S
For the electronic measurement of currents : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
IPN = 500 A
Electrical data
16137
IPN Primary nominal rms current
IP
Primary current, measuring range
RM Measuring resistance
with ± 15 V
with ± 18 V
with ± 24 V
@ ± 500 A max
@ ± 800 A max
@ ± 500 A max
@ ± 800 A max
@ ± 500 A max
@ ± 800 A max
ISN Secondary nominal rms current
K N Conversion ratio
VC Supply voltage (± 5 %)
IC
Current consumption
Accuracy - Dynamic performance data
εX G
L
Overall accuracy @ IPN , TA = 25°C
Linearity error
IO
IOT
tr
di/dt
f
Offset current @ IP = 0, TA = 25°C
Thermal drift of IO
- 40°C .. + 70°C
Response time 1) @ 90 % of IPN
di/dt accurately followed
Frequency bandwidth (- 1 dB)
General data
TA
Ambient operating temperature
TS Ambient storage temperature
R S Secondary coil resistance @
m Mass
Standards
TA = 70°C
500
A
0 .. ± 800
A
RM min
RM max
0
60
0
11
0
92
0
30
5
149
5
65
100
mA
1 : 5000
± 15 .. 24
V
24 (@ ± 18V)+ IS mA
± 0.6
%
< 0.1
%
Typ Max
± 0.4 mA
± 0.1 ± 0.4 mA
<1
> 100
DC .. 100
µs
A/µs
kHz
- 40 .. + 70
°C
- 40 .. + 85
°C
70
230
g
EN 50155 : 1995
EN 50178 : 1997
Features
Closed loop (compensated) current
transducer using the Hall effect
Insulated plastic case recognized
according to UL 94-V0.
Advantages
Excellent accuracy
Very good linearity
Low temperature drift
Optimized response time
Wide frequency bandwidth
No insertion losses
High immunity to external
interference
Current overload capability.
Applications
AC variable speed drives and servo
motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies
(SMPS)
Power supplies for welding
applications.
Applications domain
Traction
Industrial.
Note : 1) With a di/dt of 100 A/µs.
060922/9
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
page 1/3
www.lem.com

Share Link: 